CB7-125N MCB

Designed for AC 50/60 Hz circuits with rated voltage up to 400 V and current from 10 A to 125 A. The series provides overload and short-circuit protection for residential, commercial, industrial and high-rise building applications.

Standards: IEC 60947-2, IEC 60898-1

Rated current63–125 A
Poles1P / 2P / 3P / 4P
Breaking capacity6 kA
Trip curvesC / D
Request a Quote
01

General

CB7-125N miniature circuit breaker series

Operating Conditions

  1. Ambient air temperature: -5°C to +40°C, with a daily average not exceeding +35°C.
  2. Installation altitude: no more than 2,000 m above sea level.
  3. Relative humidity should not exceed 50% at +40°C. Higher humidity is permitted at lower temperatures when condensation is controlled.
  4. Installation category: III.
  5. Mount on a 35 mm DIN rail conforming to EN 60715 and TH 35-7.5 rail requirements.
  6. Pollution degree: 3.
  7. The mounting plane may deviate by no more than ±5° from vertical.
  8. Install where the product is not exposed to significant impact or vibration.
02

Selection

ModelShell grade currentBreaking capacityPolesTrip curveRated current
CB7-125N125 A6 kA1P / 2P / 3P / 4PC / D63, 80, 100, 125 A
03

Technical Parameters

CategoryParameterUnitValue
StandardReference standardIEC / EN 60947-2
Electrical featuresRated current InA63, 80, 100, 125
PolesP1, 2, 3, 4
Rated voltage UeV230 / 400
Insulation voltage UiV500
Rated frequencyHz50 / 60
Rated breaking capacityA6,000
Impulse withstand voltage UimpV6,000
Dielectric test voltage, 1 minkV2.5
Thermo-magnetic releaseC: Ii=8In / D: Ii=12In
Mechanical featuresElectrical lifeoperations1,500
Mechanical lifeoperations10,000
Contact position indicatorYes
Protection degreeIP20
Thermal reference temperature°C30
Ambient temperature°C-5 to +40
Storage temperature°C-25 to +70
04

Dimensions and Installation Sizes

CB7-125N dimensions and installation sizes in millimetres
05

Tripping Characteristics

TypeTest currentTripping timeExpected result
C, D1.05In≤1 h (In≤63 A); ≤2 h (In>63 A)Not tripping
C, D1.3In≤1 h (In≤63 A); ≤2 h (In>63 A)Tripping
C, D2.55In1 s < t < 120 sTripping
C8In × 80%≤0.2 sNot tripping
D12In × 80%≤0.2 sNot tripping
C8In × 120%<0.2 sTripping
D12In × 120%<0.2 sTripping

Confirm final specifications and order code with our sales team before purchasing.

Inside production

Factory & Production

From assembly to inspection, each stage is organized around consistent workmanship and practical quality control.

Representative imagery shown. Actual facility photography will be added when supplied.

02
Cover of the internal reading copy test reportInternal reading copy

Documentation

Product test
report copy

Test report reference ATJC2011170002700S for miniature circuit breakers. The supplied file is clearly marked as an internal reading copy and is not a valid certificate.

MCB test documentation 33-page supplied copy
View supplied report For reference only — not valid certification evidence.